4C Group save £16k+ per year with ecoDriver and CEEP for COA  

4C Group is a market-leading property developer and operator with a growing portfolio of hotels, residential andmixed-use developments across the UK, East Africa and Canada.
The Group works with major global hospitality brands, including Marriott, Hilton, IHG and Choice, and its portfoliofeatures landmark properties such as The Westin London City and Canopy by Hilton London City, among others.


Through thoughtful development, operational excellence and a commitment to sustainable growth, 4C Groupcreates exceptional places that deliver lasting value for guests, investors and local communities.

November 2026

4C Group had already made substantial steps in their sustainability journey, monitoring energy across multiple properties for years. However, they wanted to unlock further savings. Within weeks of ecoDriver’s CEEP for COA, they uncovered a misconfigured setting which could have cost over £16,000 annually in wasted energy for a single hotel alone.  

The Challenge  

Having already deployed ecoDriver to monitor the energy across several buildings, 4C Group had successfully captured initial efficiency gains and had made successful steps towards their sustainability goals. However, the team eventually hit a plateau, reaching the limit of what standard internal monitoring could achieve on its own.  

Recognising the untapped potential remaining within their granular data, and inspired by insights demonstrated during a training session with ecoDriver Low Carbon Engineer, Malcolm, the hotel’s green leads asked ecoDriver to conduct a comprehensive data audit. The objective was to dig deeper into operational schedules, heating and cooling plant efficiency, uncover hidden energy waste, and establish monthly reporting routines for property owners.  

The Approach and Method  

To maintain momentum, 4C Group partnered with ecoDriver for specialist support through ecoDriver’s “CEEP for COA” service, to implement a structured diagnostic approach and targeted interventions based on the energy data and building information. 

CEEP for COA (Collaborative Environmental Engagement Programme with Continual Operational Assurance) is a continuous operational framework beneath measured standards like NABERS UK.  It combines systematic investigation, practical improvements, ongoing monitoring, and staff engagement to eliminate energy waste, sustain savings, build operational confidence, and generate traceable audit evidence that protects building ratings year-round.  

CEEP for COA – 4C Group: Step by Step 

  • Site Visit – A visit to the hotel was carried out to understand the plant and equipment, how different areas are used, and how systems are controlled and operated, helping identify opportunities to reduce energy consumption.  
  • Data Granularity: Leveraged high-resolution half-hourly (HH) data alongside existing sub-metering feeds across the properties.  
  • Property Profiling: Collected detailed operational parameters, including hotel size, occupancy profiles, building management systems (BMS), operating manuals, and seasonal occupancy patterns.  
  • Operational Auditing: Reviewed BMS control strategies, schedules and plant operation alongside actual energy consumption data, to identify discrepancies and opportunities for improvement, ensuring systems operate efficiently and respond to building demand.  
  • Staff Involvement and Knowledge Sharing: Involve staff throughout the process, sharing how opportunities were identified, what changes were made, and why. Build their understanding of building demand and control strategies so they can sustain improvements and identify further opportunities.  

What We Found  

Starting with Canopy site, the audit uncovered critical operational anomalies that traditional top-level monitoring had missed. None of the systems had failed; rather, they were faithfully executing instructions that had drifted or been misconfigured over time.  

ecoDriver CEEP for COA identified energy saving opportunities such as AHU schedules overrunning occupancy and setpoints running hotter than required, but also identified something significant with the AHU consumption patterns: 

Overriding 24-Hour BMS Enable Settings  

  • The Issue: AHU schedules were programmed to run from 5:00 AM to midnight, but granular energy data revealed that one major AHU was running 24 hours a day, 7 days a week.  
  • Root Cause: Investigation uncovered a separate “24-hour enable” setting active within the controls, silently overriding the primary programmed schedule. This issue was subsequently identified and corrected across several other AHUs.  
  • The Impact: Eliminated an estimated 75,000 kWh per year of avoidable fan electricity, delivering an annual savings of £16,000. This accounted for fan energy only, with further reductions anticipated from avoided heating and cooling loads   

The Results  

By partnering with ecoDriver to audit their telemetry and refine their BMS schedules, 4C Group unlocked major financial and carbon savings in its Canopy site.  

  • Financial Savings: Prevented over £16,000 per year at Canopy site alone, in direct electricity and fan operational costs. 
  • Carbon Reduction: Substantially lowered overall site emissions, directly supporting corporate ESG reporting goals.  
  • Owner Reporting: Established API monthly reporting pipelines to keep property owners fully informed of performance metrics along with detailed investigation – action – savings information on the ecoDriver portal for each project.  

Maintaining Long-Term Success  

Sustainable energy management is not a one-off project; it is an ongoing discipline. Beyond reducing current consumption, 4C Group’s strategy focuses heavily on preventing energy waste from creeping back in as staff change, seasonal requirements shift, and building operations evolve. Through continuous monitoring and data-led oversight, the group ensures that efficiency gains remain permanent fixtures of their operational model.  

“The CEEP for COA team has been fantastic to work with. Their thorough, data-driven approach allowed us to dig much deeper into our Building Management System (BMS) and Air Handling Unit (AHU) operations, uncovering scheduled event functionalities we hadn’t previously realised were available. Utilising these immediately helped us eliminate unnecessary out-of-hours energy usage. Beyond quick wins, they also identified strong future investment opportunities—such as installing air quality sensors to unlock further long-term savings. 

Following this success, we plan to continue our work with CEEP for COA within our building to uncover even more savings opportunities through their expertise.” 

-Jekaterina Kolopencik, Green Champion Lead, 4C Group

Ready to uncover hidden energy waste in your portfolio?  

Book a meeting with our team today to discover how continuous operational performance assurance can transform your estate’s efficiency.  

Case Studies

Happy Clients